Brand Name : Tianan Electric

Model Number : HXGN26-12F

Certification : ISO9001:2000, VDE, CCC, TUV

Place of Origin : CHINA

MOQ : 1set

Price : Pending

Payment Terms : T/T, L/C, D/A, D/P, Western Union, MoneyGram

Supply Ability : 2000sets per year

Delivery Time : 45work days

Packaging Details : wooden cases

Service Life : 10000

Insulated Type : Gas Insulated

Application : Indoor

Altitude : ≤1000m

Contact Now

Sf6 Rmu Mv Gis Ring Main Units And Compact Switchgear Systems Ac Metal - Clad

AC Metal - clad SF6 RMU MV GIS Ring Main Units and Compact Switchgear

Overview

HXGN26-12(F) AC Metal-clad SF6 RMU Switchgear (hereinafter referred to as “RMU”), is designed and researched by our company through absorbing and digesting abroad advanced technology and combining power supply requirements of state.

Features

a. Main switch is FN26-12 SF6 load switch.

b. Three phases are longitudinal arrangement.

c. Two mechanism: manual drive, manual and motor drive.

d. Enclosure: complete aluminum zinc coated steel plate.

e. Reliable five-protection and interlock system.

f. Easy wiring connection of control circuit between cubicles.

Service condition
a. Altitude≤1000m
b. Ambient air temperature: Maximum +40ºC Minimum -35ºC
c. Relative humidity: Diary average value shall be not more than 95%; monthly average value shall be
not more than 90%.
d. Ambient air should be with no corrosion, no apparent pollution with combustible gas and etc.
e. Earthquake prevent function: process ground horizontal acceleration0.2g and vertical
acceleration0.1g at the same time, adopt resonance,sine,whip wave test, safety factor should be more
than 1.67

Parameters

Name Unit Parameters
Rated Voltage kV 12
Rated Frequency Hz 50
Rated Main Busbar Current A 630
Main Circuit, Earthing Circuit Rated Short-time Withstand Current kA/s 25/2
Main Circuit, Earthing Circuit Rated Peak Withstand Current kA 63
Main Circuit ,Earthing Circuit Rated Short-circuit Making Current kA 63
Full Capacity Breaking Times of Load Switch Times 100
Fuse Breaking Current kA 31.5 40
Service Life Times 10000
1min Power frequency withstand Voltage (r.m.s) Between Phases, to Earth/ Isolation Distance kA 42/48
Lightning Impulse Withstand Voltage (Peak) Between Phases, to Earthing/ Isolation Distance kV 75/85
Secondary Circuit 1min Power Frequency Withstand Voltage kV 2

Product Tags:

gis gas insulated switchgear

      

middle voltage switchgear

      
Quality Sf6 Rmu Mv Gis Ring Main Units And Compact Switchgear Systems Ac Metal - Clad for sale

Sf6 Rmu Mv Gis Ring Main Units And Compact Switchgear Systems Ac Metal - Clad Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Ningbo Tianan (Group) Co.,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)